Notifications
You must be signed in to change notification settings - Fork 0
/
approximated_energy_limit.m
164 lines (129 loc) · 7.45 KB
/
approximated_energy_limit.m
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
function [Energy_limit,HST_limit,AEQ_limit,TOT_limit,Energy]=approximated_energy_limit(AMB,cooling)
%% This function calculates the approximate energy limits
% Syntax of this function:
% Input data:
% AMB - profile of ambient temperature, degC
% cooling - a cooling type, string vector
% Output data:
% Energy_limit - trajectory of power loadings, pu
% HST_limit - profile of winding hot-spot temerature , degC
% TOT_limit - profile of top-oil temperature, degC
% AEQ_limit - ageing equivalent, pu relatve to normal ageing (1pu)
% Energy - amount of energy (Attention: measured in pu*min)
% Load the Temp and Ageing data (see below)
if cooling=="ONAN"
load('ONAN_temp_ageing.mat')
elseif cooling=="ONAF"
load('ONAF_temp_ageing.mat')
elseif cooling=="OF"
load('OF_temp_ageing.mat')
elseif cooling=="OD"
load('OD_temp_ageing.mat')
elseif cooling=="distribution_transformer"
load('distribution_transformer_temp_ageing.mat')
end
% Table "Temp": size 200x102 represents the Hot spot temperatures
% ---------------------------------------------------------
%| | | Ambient temperature range |
%| # |Loading | -50°C | -49°C | ...| +49°C | +50°C |
%| |---------------------------------------------------|
%| 1 |0.01 pu | HST1,°C | ... |...| ... | HST1,°C |
%| 2 |0.02 pu | HST2,°C | ... |...| ... | HST2,°C |
%|... | ... | ... | ... |...| ... | ... |
%| 200| 2 pu | HST200,°C | ... |...| ... | HST200,°C|
%----------------------------------------------------------
% Note: ambient temperature range is not included in"Temp"
% Table "Ageing": size 200x102
% ---------------------------------------------------------
%| | | Ambient temperature range |
%| # |Loading | -50°C | -49°C | ...| +49°C | +50°C |
%| |---------------------------------------------------|
%| 1 |0.01 pu | AEQ1,°C | ... |...| ... | AEQ1,°C |
%| 2 |0.02 pu | AEQ2,°C | ... |...| ... | AEQ2,°C |
%|... | ... | ... | ... |...| ... | ... |
%| 200| 2 pu | AEQ200,°C | ... |...| ... | AEQ200,°C|
%----------------------------------------------------------
% Note: ambient temperature range is not included in "Ageing"
% Define the ambient temperature range
Amb_temperature_range=-50:1:50;
% Extract the loadings 0.01 pu:2pu
Table_Loadings=Temp(:,1);
% set a HST limit for Kraft paper
HST_limit=98;%°C
% Extract unique values of initial ambient temperature vector
unique_AMB_values=unique(AMB);
%% Reconstructing the vector of PUl_final for given AMB vector
for i=1:length(unique_AMB_values)% for each unique value of ambient temperature
% Find index t of the closest value in vector Amb_temperature_range
[~,t]=min(abs(Amb_temperature_range-unique_AMB_values(i)));
if Amb_temperature_range(t)==unique_AMB_values(i)% if AMB matches the closest value in vector "Amb_temperature_range"
% Extract HST for given unique_AMB_values(i) from matrix "Temp"
Extracted_HST=Temp(:,t+1); % t+1 is required due to t==1 loadings
% Extract PUL for given AMB temperature using griddedInterpolant
[~, index] = sort(Table_Loadings);
F = griddedInterpolant(Extracted_HST(index),Table_Loadings(index));
PUL_steady_state(i)=F(HST_limit);
else % if AMB does not match the closest value in vector "Amb_temperature_range"
if Amb_temperature_range(t)>unique_AMB_values(i) % if the closest value is higher
% Example: unique_AMB_values(i)= 20.8; and Amb_temperature_range(t)=21;
% Extact the closest AMB from Amb_temperature_range
AMB1(1:length(Table_Loadings),1)=Amb_temperature_range(t);
% Extact the previous AMB from the closest value in Amb_temperature_range
AMB2(1:length(Table_Loadings),1)=Amb_temperature_range(t-1);
% Extract corresponding HST from matrix "Temp"
HST1=Temp(:,t+1);% "t+1" in Temp corresponds to "t" in Amb_temperature_range!
HST2=Temp(:,t); % "t" in Temp corresponds to "t-1" in Amb_temperature_range!
elseif Amb_temperature_range(t)<unique_AMB_values(i)% if the closest value is lower
% Example: unique_AMB_values(i)= 21.3; and Amb_temperature_range(t)=21;
% Extract the next AMB after the closest value in Amb_temperature_range
AMB1(1:length(Table_Loadings),1)=Amb_temperature_range(t+1);
% Extact the closest AMB from Amb_temperature_range.
AMB2(1:length(Table_Loadings),1)=Amb_temperature_range(t);
% Extract corresponding HST from matrix "Temp"
HST1=Temp(:,t+2);% t+2 in Temp corresponds to "t+1" in Amb_temperature_range!
HST2=Temp(:,t+1);% t+1 in Temp corresponds to "t" in Amb_temperature_range!
end % end of if Amb_temperature_range(t)>unique_AMB_values(i)
% Create vectors of ambient and HST
array_amb=[AMB2 AMB1];
array_HST=[HST2 HST1]; %[AMB2 AMB1] t+1!
% Create target vectors of given ambient temperature AMB
array_target=linspace(unique_AMB_values(i),unique_AMB_values(i),length(Table_Loadings))';
% Find the interpolated HST (vector)between given vectors HST and
% AMB for each value of Table_Loadings
for j=1:length(Table_Loadings)
HST_interpolated(j,1)=interp1(array_amb(j,:),array_HST(j,:),array_target(j,:));
end
% Change of variable name
Extracted_HST=HST_interpolated;
% Recreate PUL_steady_state for given HST_limit for a given unique value of AMB
[~, index] = sort(Table_Loadings);
F = griddedInterpolant(Extracted_HST(index),Table_Loadings(index));
PUL_steady_state(i)=F(HST_limit);
end % end of "if Amb_temperature_range(t)==unique_AMB_values(i)"
end % end of for cycle
% Reconstruct a power limit vector
for i=1:length(unique_AMB_values) % for each unique value of AMB
index=find(AMB==unique_AMB_values(i)); % find the index of the unique value in initial AMB vector
PUL_final(index)=PUL_steady_state(i); % Save PUL_steady_state for given index
end
% Change from raw vector to a column vector
Energy_limit=PUL_final'; % final output
% Calculate the energy (measured in pu*min)
Energy=sum(Energy_limit);
% Attention: Here, energy is calculated as a sum of power values over the day.
% This is possible because we assume that the power is constant over the time step
% However, if you plan to implement this code in your own research we suggest
% considering theintegral of power profile over the time to calculate the energy.
% Calculating winding and oil temperatures as well as the insulation ageing
if cooling=="ONAN"
[~,~,AEQ_limit,HST_limit,TOT_limit]=ONAN(Energy_limit,AMB);
elseif cooling=="ONAF"
[~,~,AEQ_limit,HST_limit,TOT_limit]=ONAF(Energy_limit,AMB);
elseif cooling=="OF"
[~,~,AEQ_limit,HST_limit,TOT_limit]=OF(Energy_limit,AMB);
elseif cooling=="OD"
[~,~,AEQ_limit,HST_limit,TOT_limit]=OD(Energy_limit,AMB);
elseif cooling=="distribution_transformer"
[~,~,AEQ_limit,HST_limit,TOT_limit]=distribution_transformer(Energy_limit,AMB);
end % if cooling=="ONAN"
end % end of function