doc/src/records/rsys.md

Lines changed: 3 additions & 1 deletion
Original file line numberDiff line numberDiff line change
@@ -190,7 +190,9 @@ For rsType=ASHP, Heating Seasonal Performance Factor (HSPF).
190190

191191
**rsCap47=*float***
192192

193-
For rsType=ASHP, rated heating capacity at outdoor dry-bulb temperature = 47 ^o^F. If both rsCap47 and rsCapC are autosized, both are set to the larger consistent value.
193+
For rsType=ASHP, rated heating capacity at outdoor dry-bulb temperature = 47 ^o^F.
194+
195+
If both rsCap47 and rsCapC are autosized, they are set to consistent values based on the relative values of heating and cooling loads. If the autosized capC is greater than 75% of the autosized cap47, then rsCapC is set to autosized capC and rsCap47 is derived from rsCapC. Otherwise, rsCap47 is set to 75% of autosized cap47 and rsCapC is derived from rsCap47.
194196

195197
**Units** **Legal Range** **Default** **Required** **Variability**