Skip to content

Latest commit

 

History

History
391 lines (239 loc) · 11.1 KB

power_flow.rst

File metadata and controls

391 lines (239 loc) · 11.1 KB

Power Flow

See the module pypsa.pf.

Full non-linear power flow

The non-linear power flow network.pf() works for AC networks and by extension for DC networks too (with a work-around described below).

The non-linear power flow network.pf() can be called for a particular snapshot as network.pf(snapshot) or on an iterable of snapshots as network.pf(snapshots) to calculate the non-linear power flow on a selection of snapshots at once (which is more performant than calling network.pf on each snapshot separately). If no argument is passed, it will be called on all network.snapshots.

Non-linear power flow for AC networks

The power flow ensures for given inputs (load and power plant dispatch) that the following equation is satisfied for each bus i:

S_i = P_i + j Q_i = V_i I_i^* = V_i \left(\sum_j Y_{ij} V_j\right)^*

where V_i = |V_i|e^{j\theta_i} is the complex voltage, whose rotating angle is taken relative to the slack bus.

Y_{ij} is the bus admittance matrix, based on the branch impedances and any shunt admittances attached to the buses.

For the slack bus i=0 it is assumed |V_0| is given and that \theta_0 = 0; P and Q are to be found.

For the PV buses, P and |V| are given; Q and \theta are to be found.

For the PQ buses, P and Q are given; |V| and \theta are to be found.

If PV and PQ are the sets of buses, then there are |PV| + 2|PQ| real equations to solve:

\textrm{Re}\left[ V_i \left(\sum_j Y_{ij} V_j\right)^* \right] - P_i & = 0 \hspace{.7cm}\forall\hspace{.1cm} i \in PV \cup PQ \\
\textrm{Im}\left[ V_i \left(\sum_j Y_{ij} V_j\right)^* \right] - Q_i & = 0 \hspace{.7cm}\forall\hspace{.1cm} i \in PQ

To be found: \theta_i \forall i \in PV \cup PQ and |V_i| \forall i \in PQ.

These equations f(x) = 0 are solved using the Newton-Raphson method, with the Jacobian:

\frac{\partial f}{\partial x} = \left( \begin{array}{cc}
                              \frac{\partial P}{\partial \theta} & \frac{\partial P}{\partial |V|} \\
                              \frac{\partial Q}{\partial \theta} & \frac{\partial Q}{\partial |V|}
                              \end{array} \right)

and the initial "flat" guess of \theta_i = 0 and |V_i| = 1 for unknown quantities.

Line model

Lines are modelled with the standard equivalent PI model. In the future a model with distributed parameters may be added.

If the series impedance is given by

z = r+jx

and the shunt admittance is given by

y = g + jb

then the currents and voltages at buses 0 and 1 for a line:

img/line-equivalent.png

are related by

\left( \begin{array}{c}
  i_0 \\ i_1
\end{array}
\right) =   \left( \begin{array}{cc} \frac{1}{z} + \frac{y}{2} &      -\frac{1}{z}  \\
 -\frac{1}{z} & \frac{1}{z} + \frac{y}{2}
 \end{array}
 \right)  \left( \begin{array}{c}
  v_0 \\ v_1
\end{array}
  \right)

Transformer model

The transformer models here are largely based on the implementation in pandapower, which is loosely based on DIgSILENT PowerFactory.

Transformers are modelled either with the equivalent T model (the default, since this represents the physics better) or with the equivalent PI model. The can be controlled by setting transformer attribute model to either t or pi.

The tap changer can either be modelled on the primary, high voltage side 0 (the default) or on the secondary, low voltage side 1. This is set with attribute tap_side.

If the transformer type is not given, then tap_ratio is defined by the user, defaulting to 1.. If the type is given, then the user can specify the tap_position which results in a tap ratio \tau given by:

\tau = 1 + (\textrm{tap\_position} - \textrm{tap\_neutral})\cdot \frac{\textrm{tap\_step}}{100}

For a transformer with tap ratio \tau on the primary side tap_side = 0 and phase shift \theta_{\textrm{shift}}, the equivalent T model is given by:

img/transformer-t-equivalent-tap-hv.png

For a transformer with tap ratio \tau on the secondary side tap_side = 1 and phase shift \theta_{\textrm{shift}}, the equivalent T model is given by:

img/transformer-t-equivalent-tap-lv.png

For the admittance matrix, the T model is transformed into a PI model with the wye-delta transformation.

For a transformer with tap ratio \tau on the primary side tap_side = 0 and phase shift \theta_{\textrm{shift}}, the equivalent PI model is given by:

img/transformer-pi-equivalent-tap-hv.png

for which the currents and voltages are related by:

\left( \begin{array}{c}
  i_0 \\ i_1
\end{array}
\right) =   \left( \begin{array}{cc}  \frac{1}{z} + \frac{y}{2} &      -\frac{1}{z}\frac{1}{\tau e^{-j\theta}}  \\
 -\frac{1}{z}\frac{1}{\tau e^{j\theta}} & \left(\frac{1}{z} + \frac{y}{2} \right) \frac{1}{\tau^2}
 \end{array}
 \right)  \left( \begin{array}{c}
  v_0 \\ v_1
\end{array}
  \right)

For a transformer with tap ratio \tau on the secondary side tap_side = 1 and phase shift \theta_{\textrm{shift}}, the equivalent PI model is given by:

img/transformer-pi-equivalent-tap-lv.png

for which the currents and voltages are related by:

\left( \begin{array}{c}
  i_0 \\ i_1
\end{array}
\right) =   \left( \begin{array}{cc} \left(\frac{1}{z} + \frac{y}{2} \right) \frac{1}{\tau^2} &      -\frac{1}{z}\frac{1}{\tau e^{-j\theta}}  \\
 -\frac{1}{z}\frac{1}{\tau e^{j\theta}} & \frac{1}{z} + \frac{y}{2}
 \end{array}
 \right)  \left( \begin{array}{c}
  v_0 \\ v_1
\end{array}
  \right)

Non-linear power flow for DC networks

For meshed DC networks the equations are a special case of those for AC networks, with the difference that all quantities are real.

To solve the non-linear equations for a DC network, ensure that the series reactance x and shunt susceptance b are zero for all branches, pick a Slack bus (where V_0 = 1) and set all other buses to be 'PQ' buses. Then execute network.pf().

The voltage magnitudes then satisfy at each bus i:

P_i  = V_i I_i = V_i \sum_j G_{ij} V_j

where all quantities are real.

G_{ij} is based only on the branch resistances and any shunt conductances attached to the buses.

Inputs

For the non-linear power flow, the following data for each component are used. For almost all values, defaults are assumed if not explicitly set. For the defaults and units, see :doc:`components`.

bus.{v_nom, v_mag_pu_set (if PV generators are attached)}

load.{p_set, q_set}

generator.{control, p_set, q_set (for control PQ)}

storage_unit.{control, p_set, q_set (for control PQ)}

store.{p_set, q_set}

shunt_impedance.{b, g}

line.{x, r, b, g}

transformer.{x, r, b, g}

link.{p_set}

Note that the control strategy for active and reactive power PQ/PV/Slack is set on the generators NOT on the buses. Buses then inherit the control strategy from the generators attached at the bus (defaulting to PQ if there is no generator attached). Any PV generator will make the whole bus a PV bus. For PV buses, the voltage magnitude set point is set on the bus, not the generator, with bus.v_mag_pu_set since it is a bus property.

Note that for lines and transformers you MUST make sure that r+jx is non-zero, otherwise the bus admittance matrix will be singular.

Outputs

bus.{v_mag_pu, v_ang, p, q}

load.{p, q}

generator.{p, q}

storage_unit.{p, q}

store.{p, q}

shunt_impedance.{p, q}

line.{p0, q0, p1, q1}

transformer.{p0, q0, p1, q1}

link.{p0, p1}

Linear power flow

The linear power flow network.lpf() can be called for a particular snapshot as network.lpf(snapshot) or on an iterable of snapshots as network.lpf(snapshots) to calculate the non-linear power flow on a selection of snapshots at once (which is more performant than calling network.lpf on each snapshot separately). If no argument is passed, it will be called on all network.snapshots.

For AC networks, it is assumed for the linear power flow that reactive power decouples, there are no voltage magnitude variations, voltage angles differences across branches are small and branch resistances are much smaller than branch reactances (i.e. it is good for overhead transmission lines).

For AC networks, the linear load flow is calculated using small voltage angle differences and the series reactances alone.

It is assumed that the active powers P_i are given for all buses except the slack bus and the task is to find the voltage angles \theta_i at all buses except the slack bus, where it is assumed \theta_0 = 0.

To find the voltage angles, the following linear set of equations are solved

P_i = \sum_j (KBK^T)_{ij} \theta_j - \sum_l K_{il} b_l \theta_l^{\textrm{shift}}

where K is the incidence matrix of the network, B is the diagonal matrix of inverse branch series reactances x_l multiplied by the tap ratio \tau_l, i.e. B_{ll} = b_l = \frac{1}{x_l\tau_l} and \theta_l^{\textrm{shift}} is the phase shift for a transformer. The matrix KBK^T is singular with a single zero eigenvalue for a connected network, therefore the row and column corresponding to the slack bus is deleted before inverting.

The flows p0 in the network branches at bus0 can then be found by multiplying by the transpose incidence matrix and inverse series reactances:

F_l = \sum_i (BK^T)_{li} \theta_i - b_l \theta_l^{\textrm{shift}}

For DC networks, it is assumed for the linear power flow that voltage magnitude differences across branches are all small.

For DC networks, the linear load flow is calculated using small voltage magnitude differences and series resistances alone.

The linear load flow for DC networks follows the same calculation as for AC networks, but replacing the voltage angles by the difference in voltage magnitude \delta V_{n,t} and the series reactance by the series resistance r_l.

Inputs

For the linear power flow, the following data for each component are used. For almost all values, defaults are assumed if not explicitly set. For the defaults and units, see :doc:`components`.

bus.{v_nom}

load.{p_set}

generator.{p_set}

storage_unit.{p_set}

store.{p_set}

shunt_impedance.{g}

line.{x}

transformer.{x}

link.{p_set}

Note that for lines and transformers you MUST make sure that x is non-zero, otherwise the bus admittance matrix will be singular.

Outputs

bus.{v_mag_pu, v_ang, p}

load.{p}

generator.{p}

storage_unit.{p}

store.{p}

shunt_impedance.{p}

line.{p0, p1}

transformer.{p0, p1}

link.{p0, p1}