Troubleshooting

Library dependency issues

If you are experiencing problems with PyPSA or with the importing of the libraries on which PyPSA depends, please first check that you are working with the latest versions of all packages.

See :ref:`upgrading-packages` and :ref:`upgrading-pypsa`.

Consistency check on network

Running network.consistency_check() will examine the network components to make sure that all components are connected to existing buses and that no impedances are singular.

Problems with power flow convergence

If your network.pf() is not converging there are two possible reasons:

  • The problem you have defined is not solvable (e.g. because in reality you would have a voltage collapse)
  • The problem is solvable, but there are numerical instabilities in the solving algorithm (e.g. Newton-Raphson is known not to converge even for solvable problems; or the flat solution PyPSA uses as an initial guess is too far from the correction solution because of transformer phase-shifts)

There are some steps you can take to distinguish these two cases:

  • Check the units you have used to define the problem are correct; see :doc:`conventions`. If your units are out by a factor 1000 (e.g. using kW instead of MW) don't be surprised if your problem is no longer solvable.
  • Check with a linear power flow network.lpf() that all voltage angles differences across branches are less than 40 degrees. You can do this with the following code:
import pandas as pd, numpy as np

now = network.snapshots[0]

angle_diff = pd.Series(network.buses_t.v_ang.loc[now,network.lines.bus0].values -    network.buses_t.v_ang.loc[now,network.lines.bus1].values,index=network.lines.index)

(angle_diff*180/np.pi).describe()
  • You can seed the non-linear power flow initial guess with the voltage angles from the linear power flow. This is advisable if you have transformers with phase shifts in the network, which lead to solutions far away from the flat initial guess of all voltage angles being zero. To seed the problem activate the use_seed switch:
network.lpf()
network.pf(use_seed=True)
  • Reduce all power values p_set and q_set of generators and loads to a fraction, e.g. 10%, solve the load flow and use it as a seed for the power at 20%, iteratively up to 100%.

Pitfalls/Gotchas

Some attributes are generated dynamically and are therefore only copies. If you change data in them, this will NOT update the original data. They are all defined as functions to make this clear.

For example:

  • network.branches() returns a DataFrame which is a concatenation of network.lines and network.transformers
  • sub_network.generators() returns a DataFrame consisting of generators in sub_network

Reporting bugs/issues

Please do not contact the developers directly.

Please report questions to the mailing list.

If you're relatively certain you've found a bug, raise it as an issue on the PyPSA Github Issues page.