This issue coordinates subtasks to achieve stable grids resulting from a Ding0. "Stable" refers to grids that do not exceed their hosting capacity and do not violate operational constraints like voltage band and line loading.
Problem description
When analyzing grid reinforcement needs with eDisGo, voltage at some nodes exceeds +/-10 % of nominal voltage which leads to identified grid reinforcement needs.
The investigation is done using grid 1882 of Ding0 data version 20180219182404.
Tasks
Notes
Operational constraints regarding voltage are differently defined in Ding0 and eDisGo. Whereas eDisGo simply requires no exceedance of +/-10 % of nominal voltage, Ding0 splits MV and LV level and thus applies strong limits for each grid level which makes sure +/- 10 % is not violated.
Voltage limits Ding0
| Grid level |
Load case |
Feed-in case |
| MV |
5 % |
2 % |
| LV |
5 % |
3 % |
See also
This issue coordinates subtasks to achieve stable grids resulting from a Ding0. "Stable" refers to grids that do not exceed their hosting capacity and do not violate operational constraints like voltage band and line loading.
Problem description
When analyzing grid reinforcement needs with eDisGo, voltage at some nodes exceeds +/-10 % of nominal voltage which leads to identified grid reinforcement needs.
The investigation is done using grid 1882 of Ding0 data version 20180219182404.
Tasks
Notes
Operational constraints regarding voltage are differently defined in Ding0 and eDisGo. Whereas eDisGo simply requires no exceedance of +/-10 % of nominal voltage, Ding0 splits MV and LV level and thus applies strong limits for each grid level which makes sure +/- 10 % is not violated.
Voltage limits Ding0
See also