Modbus Setup

Last Updated: June. 18, 2024

Table of Contents


Modbus ID Range

Total 1 ~ 247 (0x01 ~ 0xF7)

  • [01 ~ 30 (0x01 ~ 0x1E)] PV Inverter
  • [31 ~ 60 (0x1F ~ 0x3C] PV Temperature
  • [61 (0x3D)] GHI : Renke Pyranometer RS-TBQ-N01-AL
  • [62 (0x3E)] GHI : EKO Pyranometer MS-80SH
  • [63 (0x3F)] GHI : INFWIN PYR20-AAC002
  • [71 ~ 80 (0x47 ~ 0x50)] POA
  • [73 (0x49)] POA : INFWIN PYR20-AAC002
  • [90 ~ 100 (0x5A ~ 0x64)] Structure Sensor
  • [200 (0xC8)] Wind Direction
  • [201 (0xC9)] Wind Speed
  • [202 (0xCA)] Ambient Temperature

MBControl Default

Wire (LAPP 1032100)

	White	Vcc
	Brown	GND
	Green	A+
	Yellow  B-

Modbus Parameters

Use Function 16 (0x10) (Write Multiple Registers) to Write and Save parameters. Once rebooting it takes effect.

Address 100 (0x0064) [U16] Modbus ID 1 ~ 247
Address 101 (0x0065) [U16] Baud rate: 0=4800, 1=9600, 2=19200
Address 102 (0x0066) [U16] Parity: 0=None, 1=Odd, 2=Even
Address 103 (0x0067) [U16] Stop bits: 1 (Fix)
Address 104 (0x0068) [U16] Temperature Unit: 0=°C, 1=°K, 2=°F
Address 105 (0x0069) [U16] Save Parameters: 1, Write Only
  • Example: ID=71(0x47), Baud=9600, No Parity, 1 Stop bit, °C
  Send: 06 10 0064 0006 0C 0047 0001 0000 0001 0000 0001 [CRC]
  Receive: 06 10 00 64 00 06 [CRC]

EKO Pyranometer MS-80SH

GHI measurement. Set the Modbus ID and RS485 parameters in Hibi software supplied by EKO.

  • Address 2, 3 : [F32] Adjusted solar radiation intensity (W/m²)
  • Example: 3.6 W/m² (0x4064959C = 3.57163)
  Send: 3E 03 0002 0002 [CRC]
  Receive: 3E 03 04 40 64 95 9C [CRC]

MBControl Solar Irradiance Sensor MBMet-500-AB

POA measurement.

  • Address 0 : [U16] Solar irradiation (W/m²)
  • Example: 7 W/m² (0x0007 = 7)
  Send: 47 03 0000 0001 [CRC]
  Receive: 47 03 02 00 07 [CRC]

MBControl PV Module Temperature Sensor MBMet-830

PV Module Temperature measurement.

  • Address 0 : [S16] 10x Temperature (°C)
  • Example: 24.9°C (0x00F9 = 249)
  Send: 1F 03 0000 0001 [CRC]
  Receive: 1F 03 02 00 F9 [CRC]

MBControl Wind Speed Sensor MBMet-100B-B

Wind Speed measurement.

  • Address 0 : [U16] 10x Wind Speed (m/s)
  • Example: 3.2 m/s (0x0020 = 32)
  Send: 01 03 0000 0001 [CRC]
  Receive: 01 03 02 00 20 [CRC]

PUSR Default

3.81mm pitch 5P

Local Image


GA Default

3.50mm pitch 5P

Local Image


CWT(ComWinTop) Temperature Sensors

CWT-TH04S-M (Ambient Temperatrure) / CWT-T02S (PV-module Temperature)

DC Power: 12V (5 ~ 30V dc)

Wire

	Brown	Vcc
	Black	GND
	Yellow	A+
	Blue	B-

Modbus-RTU

  Default parameter 4800bps, 1S, NP, 8bits 
  Default address 0x01

Baud Rate

  • Address: 0x07D1
  • Function: 6 / 3
  • Content:
 baud rate: 
	    0 – 2400bps
	    1 – 4800bps (*)
	    2 – 9600 bps

Modbus ID

  • Address: 0x07D0
  • Function: 3 / 6
  • Example: ID = 0x1F(31)(Tpv), 0xCA(202)(Ta)

Use CWT-THXXS Config Tool for baud and ID

CWT Temperature measurement

  • Address 1 (0x0001) : [S16] 10x Temperature
  • Example: PV Temperature = 28.0°C (0x118 = 280)
  Send: 1F 03 0001 0001 [CRC] 
  Receive: 1F 03 02 01 18 [CRC]
  • Example: Ambient Temperature = 27.5 (0x0113 = 275)
  Send: CA 03 0001 0001 [CRC] 
  Receive: CA 03 02 01 13 [CRC]

INFWIN PYR20-AAC002

DC Power: 12V (3.9 ~ 30V dc)

Wire

	Red	Vcc
	Black	GND
	Yellow	A+
	White   B-

Modbus-RTU

  Default parameter 9600bps, 1S, NP, 8bits 
  Default address 0x01

Modbus ID

  • Address: 0x0200
  • Function: 3 / 6 / 16
  • Example: ID = 0x3F(63) (GHI), 0x49(73) (POA)
  Send: 01 06 0200 003F [CRC]
  Receive: 01 06 02 00 00 3F [CRC] 

Take effect once re-power on

GHI measurement.

  • Address 0 : [U16] Solar radiation intensity (W/m²)
  • Example: 16 W/m² (0x0010 = 16)
  Send: 3F 03 0000 0001 [CRC]
  Receive: 3F 03 02 00 10 [CRC]

MRT Default

Wire

	Red             Vcc
	Black           GND
	Green(Yellow)	A+
	White           B-

Renke Default

3 Way Cable:

https://youtu.be/ZsB1V8zTqgs?t=33

DC Power: 12V (10 ~ 30V dc)

Wire

	Brown	Vcc
	Black	GND
	Yellow	A+
	Blue    B-

Modbus-RTU

  Default speed   4800bps
  Default address 0x01

Default Command

Version Number

  • Address: 0x0009
  • Function: 0x03
  • Example: V2.04
  Send: 01 03 0009 0001 [CRC]
  Receive: 01 03 02 02 04 [CRC]

Modbus ID

  • Address: 0x07D0
  • Function: 0x06 / 0x03
  • Example: ID = 0x00C8
  Send: C8 06 07D0 00C8 [CRC]
  Receive: C8 06 07 D0 00 C8 [CRC] // Echo

Query Modbus ID (0xFF)

  • Address: 0x07D0
  • Function: 0x03
  • Example: ID = 0x003D
  Send: FF 03 07D0 0001 [CRC]
  Receive: 3D 03 02 00 3D [CRC]

Baud Rate

  • Address: 0x07D1
  • Function: 0x06 / 0x03
  • Content:
 baud rate: 
	    0 – 2400bps
	    1 – 4800bps
	    2 – 9600 bps
	    3 – 19200bps 
  • Example: Baud = 9600 bps
  Send: C8 06 07D1 0002 [CRC]
  Receive: C8 06 07 D1 00 02 [CRC] // Echo

Renke Pyranometer RS-TBQ-N01-AL

GHI measurement.

  • Address 0 : [U16] Solar radiation intensity (W/m²)
  • Example: 16 W/m² (0x0010 = 16)
  Send: 3D 03 0000 0001 [CRC]
  Receive: 3D 03 02 00 10 [CRC]

Renke Wind Direction

  • Address 0 : [U16] Wind direction 0 ~ 7
  • Address 1 : [U16] Wind direction 0 ~ 360°

Renke Wind Speed

  • Address 0 : [U16] 10x Wind Speed (m/s)
  • Example: Wind Speed = 2.9 m/s (0x1D = 29)
  Send: C9 03 0000 0001 [CRC]
  Receive: C9 03 02 00 1D [CRC]

Renke Ambient Temperature

  • Address 505 (0x01F9) : [S16] 10x Ambient Temperature
  • Example: Ambient Temperature = 22.4°C (0xE0 = 224)
  Send: CA 03 01 F9 00 01 [CRC] 
  Receive: CA 03 02 00 E0 [CRC]
  • Example: Ambient Temperature = -10.1°C (0xFF9B = -101)
  Send: CA 03 01 F9 00 01 [CRC] 
  Receive: CA 03 02 FF 9B [CRC]

Renke Weather Station

Wind Speed

  • Modbus ID: 01 (*)
  • Baud: 4800 (*)

Wind Direction

  • Modbus ID: 02 (*)
  • Baud: 4800 (*)

Base Station

  • Modbus ID: 01 --> 202 (0xCA)
  • Baud: 4800 --> 9600

Address Map

  • 500 (0x1F4) : [U16] 10x Wind Speed
  • 502 (0x1F6) : [U16] Wind Direction (0~7)
  • 503 (0x1F7) : [U16] Wind Direction (0~360°)
  • 504 (0x1F8) : [U16] 10x Humidity
  • 505 (0x1F9) : [S16] 10x Ambient Temperature (°C)

Renke 4-20mA RS485

  • I/O : 4~20mA / 655~3276 (12bit)
  • Address 00 : IN0
  • Address 01 : IN1
  • Example: Read IN0 (0x78A = 1930)
  Send: 5A 03 00 00 00 01 [CRC] 
  Receive: 5A 03 02 07 8A [CRC] 